Application and Operation Principles
FL-2R : Once the supply voltage is applied.
The relay is switched on within "ton " time period.
At the end of " ton " period the relay switches off
and keeps the position within " toff " period.
At the end of " toff " period the relay switches on again.
FL-R : Is delay-time adjustable [(t) 0.1-12 sn.] In between two impulses.
The relay is switched off when the supply voltage is applied
and keeps the position within “t” time period.
At the end of “t” time period the relay switches
on and waits for 0.5 second. After the end of 0.5 second
the relay switches off again. FL-RT: FL-RT has a triac output in comparison with FL-R.
FL-V2R : FL-V2R is used to operate and pause the
machines in certain period of times or upon the
request of the proposed time periods.
Once the voltage supply is applied the relay is switched on.
The relay switches off when “ton” time period ends.
The relay is inactive until the “toff” time period ends and
the relay switches on and keeps counting as much
as “ton” time duration.
FL-V2R is used in oiling systems, signalisations, signal lamps,
incubation machines, etc.
SX-2R : Designed to use for a purpose to inverse the direction of
rotating machines in industrial automation systems.
Once the supply voltage is applied Left-relay is switched on
after 6 second then is switched off at the end of the adjusted time period.
It waits for 6 second upon which the right-relay is to be switched on.
The relay switches off at the end of the adjusted time and waits for
6 second in order to have the left-relay switched on.
It repeats the function systematically.
Technical data for FL-2R
• Supply Voltage : 220-240V AC 50-60Hz
24V AC-DC
• Setting Error :+5% • Contact Output : 220 VAC-5A • Operation temperature : -40C ... +55C
• Net Weight : 150 gr
Technical
data for FL-R
• Supply
Voltage : 220-240 V AC 50-60 Hz
• Sensitivity : +0.1%
• Contact Output : 250 V AC - 5A
• Operation Temperature : -40C ... +55C
• Net Weight :125 gr
Technical
data for FL-V2R
• Supply
Voltage : 220-240 V AC 50-60 Hz
24
V AC - DC
• Sensitivity : +0.1%
• Contact Output : 250 V AC - 5A
• Operation Temperature : -40C ... +55C
• Net Weight :75 gr
Technical
data for SX-2R
• Supply
Voltage : 220-240 V AC 50-60 Hz
• Sensitivity : +0.1%
• Contact Output : 250 V AC - 5A
• Operation Temperature : -40C ... +55C
• Net Weight :125 gr |